Sauermann DBM 620A Removable Bluetooth Micromanometer for Air Flow Hood
Sauermann DBM 620A Bluetooth micromanometer. Differential pressure -2500 to 2500 Pa with app-based airflow readout.
$1,117.42 USD
Prices in USD, shipping not included.
Shipping cost, lead time and availability are confirmed in your quotation.
Specifications
- Removable wireless micromanometer module for the Sauermann air flow hood; also works standalone with a Pitot tube, Debimo blade or DBM VMG velocity grid
- Measures airflow, air velocity, temperature and humidity; readings shown in the SmartKap app (iOS / Android) as live values, table or graph, with PDF report generation
- Applications: thermal comfort evaluation, HVAC/R testing, HVAC/R system adjusting and balancing, air volume measurements
- Functions: section and unit selection, point/point, automatic or automatic point/point average, hold, min/max, standardized airflow, K factor, pressure integration (0 to 9), automatic autozero
- Temperature and atmospheric pressure compensation (manual or automatic for atmospheric pressure)
- Pressure: -2500 to +2500 Pa (-10 to 10 inWg), accuracy ±0.2% of reading
- Airflow (calculated): 35 to 4250 m³/h (21 to 2501 CFM), accuracy ±3% of measurement
- Air velocity (calculated): 0.2 to 10 m/s (39 to 1969 ft/min), accuracy ±3% of measurement
- Temperature (NTC): -20 to 70 °C (-4 to 158 °F), accuracy ±0.2 °C (±0.36 °F)
- Relative humidity: 0 to 100% RH, accuracy ±1.5% RH; atmospheric pressure: 700 to 1100 mbar, accuracy ±3 mbar
- Wireless: Class 1 BLE 4.2, 2.4 GHz, range up to 98 ft (30 m); requires Android 7.1 or iOS 12.4 minimum
- Power: 4 x LR6 AA alkaline batteries, up to 30 hours; adjustable auto-shut-off 0 to 60 minutes
- Housing: shock-proof ABS, IP40; maximum operating pressure 500 mbar
- Dimensions: folded 475 x 455 x 255 mm; mounted 610 x 610 x 980 mm
- Directives: 2011/65/EU RoHS II, 2012/19/EU WEEE, 2014/53/EU RED
- In the box: DBM 620A, 2 x 0.08 m silicone tube, calibration certificate
Specifications are provided by the manufacturer and may change. Please confirm the exact model in your quote request.