TSI/Alnor EBT731 Balometer Capture Hood
TSI/Alnor EBT731 Balometer capture hood. Direct air volume readings at diffusers and grilles, 25 to 2500 ft3/min (42 to 4250 m3/h).
$3,510.00 USD
Prices in USD, shipping not included.
Shipping cost, lead time and availability are confirmed in your quotation.
Specifications
- Electronic air balancing instrument used mainly to take direct air volume readings at diffusers and grilles
- Kit includes a detachable micromanometer that accepts optional probes (sold separately)
- Applications: test and balance, commissioning, facilities management, health and safety, ventilation systems, HVAC/R
- Lightweight ergonomic hood for one-person operation
- Automatic sensing and display of supply or return flow
- Back pressure compensation for accurate readings at high flow rates
- Multiple hood sizes available for different outlet dimensions
- Capture hood stand allows reaching diffusers up to 15 ft (4.5 m) without a ladder
- Micromanometer: auto-zeroing pressure sensor, automatic density correction, backlit graphic display with up to five simultaneous measurements, Log-Tchebycheff duct traverse application
- Bluetooth two-way communication; works with LogDat Mobile Remote Reader and Data Logger Software for Android devices
- Volume: 25 to 2500 ft3/min (42 to 4250 m3/h), accuracy ±3% of reading ±7 ft3/min (±12 m3/h) above 50 ft3/min (85 m3/h)
- Velocity: pitot probes 25 to 15,500 ft/min (0.125 to 78 m/s); air flow probe 25 to 5000 ft/min (0.125 to 25 m/s)
- Differential pressure: ±15 inH2O (±3735 Pa), accuracy ±2% of reading ±0.0001 inH2O (±0.025 Pa)
- Absolute pressure: 15 to 40 inHg (356 to 1016 mmHg)
- RH: 5 to 95% RH, ±3% RH (temperature/RH probe)
- Temperature: 14 to 140°F (-10 to 60°C) with probe, ±0.5°F (±0.3°C)
- Data storage: 25,500 samples, time and date stamped; power 4 x AA cells or AC adapter
- Weight: 7.4 lbs (3.4 kg)
- In the box: capture hood base with poles, frame and fabric, micromanometer, 2 x calibration certificates (pressure and flow), 6 x support poles, pitot probe, 2 x static pressure probes
Specifications are provided by the manufacturer and may change. Please confirm the exact model in your quote request.